CENTRAL PLANT – CENTRAL UTILITIES
Ocean Medical Center
DETAILS:
OCEAN MEDICAL CENTER
BRICK, NJ
CHILLER PLANT & COOLING TOWER REPLACEMENT
As part of the 43 million expansion and renovation, we were retained for the integration and replacement of two (2) chiller plants at the Ocean Medical Center. The original building’s (1984 South Wing) plant contained two (2) 235-ton electric centrifugal chillers with R-11 (CFC) refrigerant and two (2) outdoor counter-flow cooling towers.
Read More
As a result, during the expansion and renovation project, K&L Group was selected to perform a feasibility study and system design to improve the efficiency and redundancy of the chiller plant and CHW distribution system. Consideration was given to the upsizing of various chillers, the design of a primary-secondary pumping system, replacement of pumps, controls and piping, cooling towers and the elimination of CFC refrigerants. A life cycle analysis was performed using all available input including operating, maintenance, and energy costs, installed costs and life expectancies for different equipment. The analysis gave consideration to a forthcoming East Wing building addition along with various phasing issues for construction and start-up. The study and design resulted in the determination that the two (2) 235-ton CFC chillers should be replaced with new 375-ton electric centrifugal chillers, running R-134A (HFC) refrigerant. A new primary-secondary piping loop was also constructed in order to achieve the full benefit of diversity and load sharing amongst the Medical Center’s two (2) wings, as well as to support the forthcoming East Wing building addition. The system consisted of new pumps, controls, chiller plant piping, cooling towers (4 cells with variable speed drives) and underground secondary loop piping.
Project completed by K&L Group, A Division of MG Engineering
Close











